Operating voltage / quiescent
current:
Siemens/Cerberus type 20 V / max. 4.5 mA
SynoLINE300 type 20 V / max. 17 mA
Line resistance / line capacitance:
Without safety barrier SB3 ≤150 Ω / ≤1 μF
With safety barrier SB3 ≤ 50 Ω / 4 µF
Alarm activation:
Siemens/Cerberus type 680 Ω resistor or 5.6 V Zener diode
SynoLINE300 type Resistance: 410…600 Ω
Alarm voltage 4…14 V
Alarm current:
Siemens/Cerberus type < 10 mA
SynoLINE300 type <17 mA
Reset voltage < 1 V
Reset time <3 s
Settling time following a reset 10 s
Flashing current Approx. 80 mA
End-of-line (EOL)
Transzorb diode (20 V ±5%; 1.5 kW pulse
power)
EOL22(Ex) end-of-line; obligatory for ex lines
Monitored for:
Open line
Short-circuit
Ground fault monitoring (both inputs/outputs
jointly)
Suppression of erroneous
information
Continuous analysis
Message evaluation for:
Alarms 1 s (can be increased by the alarm response
time)
Faults 1 s (can be increased by the filter time)
Ground fault 60 s
Compatibility
Collective Siemens/Cerberus
Collective SynoLINE300
Refer to the 'List of compatibility' and the 'Annex'
chapter for details