23/73
Building Technologies Division Basic Documentation LME39… CC1P7106en
6 Technical data 08.12.2017
6.2 Signal cable AGV50... display BCI
Signal cable
Color white
Unshielded
Conductor 4 x 0.141 mm²
with RJ11-plug
Cable length
- AGV50.100
1 m
Location Under the burner hood (extra measures
required for compliance with
SKII EN 60730-1)
6.3 Environmental conditions
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+70 °C
Humidity <95% r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions Class 2K3
Mechanical conditions Class 2M2
Temperature range -20...+70 °C
Humidity <95% r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60 °C
Humidity <95% r.h.
Installation altitude Max. 2,000 m above sea level
Attention!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
Connectable conductor cross-sections
Terminals 1...12 Min. 0.5 mm²
Max. 1.5 mm²
Wire or stranded wire with ferrules
Auxiliary terminals N, PE, 31, 32 Min. 0.5 mm²
Max. 1.5 mm²
Wire or stranded wire with ferrules
(when connecting 2 wires or stranded
wires per terminal, the same cross-
sectional areas must be used for each
terminal)
AGK11...