8/73 
Building Technologies Division  Basic Documentation LME39…  CC1P7106en 
  1 Safety notes  03.02.2016 
1.4 Installation notes 
 
  Always run the high voltage ignition cables separate from the unit and other cables 
while observing the greatest possible distance 
  Do not mix up live and neutral conductors 
  Install switches, fuses and earthing, in compliance with local regulations 
  The connection diagrams show the burner controls with earthed neutral conductor. 
In networks with nonearthed neutral conductor and ionization current supervision, 
terminal 2 must be connected to the earth conductor via an RC unit (product no.  
ARC 4 668 9066 0). It must be made certain that local regulations are complied with 
(e.g. protection against electric shock hazard) since AC 120 V (50/60 Hz) or AC 230 V 
(50/60 Hz) mains voltage produces peak leakage currents of 2.7 mA 
  Make certain that the maximum permissible current rating of the connection terminals 
will not be exceeded 
  Do not feed external mains voltage to the control outputs of the unit. When testing the 
devices controlled by the burner control (fuel valves, etc.), the burner control must not 
be connected 
  Check the connecting lines of the air pressure switch for short-circuits (air pressure 
switch between terminals 2 and 6). If this is not observed, there is a risk of loss of 
safety functions 
  To prevent mixup of different types of burner controls, the LME39... must always be 
used in connection with grey plug-in bases AGK11.6. Make absolutely certain that 
the live conductor for the control thermostat or pressurestat is tapped after the gas 
pressure switch and the safety limit thermostat to be connected to terminal 11 (refer 
to Connection diagram) 
  For safety reasons, feed the neutral conductor to terminal 2. Connect the burner 
components (fan, ignition transformer and fuel valves) to the neutral distributor as 
shown below in the figure. The connection between neutral conductor and terminal 2 
is prewired in the base 
 
Example 
 
Z
M
N
 
Figure 1: Correct wiring of neutral conductors! 
 
 
 
 
Note! 
In extremely EMC-stressed environments, burners without fan motor or burners 
equipped with fan control via auxiliary contactor should use an AGK25 to produce a 
burden on terminal 3. If not observed, the burner is not reliably started up 
 
Recommendation: 
Legend 
V... Fuel valve 
M Fan motor 
Z Ignition transformer