66/73 
Building Technologies Division  Basic Documentation LME39…  CC1P7106en 
  22 Parameter list  08.12.2017 
22 Parameter list 
22.1 LME39.100...  
 
Parameter 
number 
Parameter  Edit  Value range  Increment  Default setting  Password level 
reading from 
level 
Password level 
writing from level 
Min.  Max. 
000  Internal parameters               
41  Heating engineer’s password (4 characters) Edit xxxx xxxx 1 --- --- OEM 
42  OEM’s password (5 characters)  Edit  xxxxx  xxxxx  1  ---  ---  OEM 
           
100  General               
102  Identification date  Read only  ---  ---  ---  ---  Info  --- 
103  Identification number  Read only  0  9999  1  0  Info  --- 
113 
Burner identification  AZL2: 
Readable 
ACS410: 
Selectable 
0  99999999  1  burnEr Id  Info  OEM via ACS410 
164  Number of startups   Resettable  0  999999  1  0  Info  Info 
166  Total number of startups  Read only  0  999999  1  0  Info  --- 
           
200  Burner control               
224  Max. time until air pressure on  Edit  0 s  179.487 s  4.851 s  179.487 s  SO  OEM 
225  Prepurge time  Edit  0 s  74.97 s  0.294 s  32.34 s  SO  OEM 
226 Preignition time  Edit 1.176 s  37.485 s  0.147 s  3.234 s  SO  OEM 
228  Flame detection time  Edit  0 s  1.47 s  0.147 s  0.294 s  SO  OEM 
230  Interval: Ignition OFF until fuel valve 2 (BV2) release  Edit  1.176 s  74.97 s  0.294 s  9.996 s  SO  OEM 
234  Postpurge time  Edit  0 s  1237.005 s  4.851 s  0 s  SO  OEM 
240 
Repetition limit value loss of flame and no flame at the end of safety 
time 
0 = none 
1 = none 
2 = 1 x repetition 
3 = 2 x repetition 
4 = 3 x repetition 
Edit 0  4  1  1  SO  OEM 
257  Postignition time  Edit  0 s  37.485 s  0.147 s  2.205 s  SO  OEM 
259  Programmed actuator opening time  Edit  0 s  74.97 s  0.294 s  32.34 s  SO  OEM 
260  Programmed actuator closing time  Edit  0 s  74.97 s  0.294 s  32.34 s  SO  OEM