44/73 
Building Technologies Division  Basic Documentation LME39…  CC1P7106en 
  15 Operation  08.12.2017 
15.1.3  Display of operating position 
 
 
P
Vh
mi n
s%
Bild 14/0707
 
Display oP: P1 stands for stage 1. 
The display following oP is unit-specific. 
 
 
P
Vh
mi n
s%
Bild 15/0707
 
Display oP: P2 stands for stage 2. 
The display following oP is unit-specific. 
 
15.1.4  Fault status messages, display of errors and info 
15.1.4.1.  Display of errors (faults) with lockout 
 
 
P
Vh
mi n
s%
Bild 185/1107
 
The display shows Loc:. The bar under the fault status 
message 
 appears. 
 
The unit is in the lockout position. 
 
The current error code is displayed (refer to Blink code 
table). 
 
Example: Error code 7 
 
15.1.4.2. Reset 
 
reset
 
1 s 
When pressing 
reset
 for 1 second, rESEt appears on the 
display. 
 
When the button is released, the basic unit will be reset. 
 
reset
 
<3 s 
 
 
P
Vh
mi n
s%
Bild 21/0707
 
 
P
Vh
mi n
s%
Bild 22/0707
 
When pressing 
reset
 for >3 seconds, the display shows 
InFo, SEr and then OPErAtE. 
 
When the button is released, the basic unit will be reset. 
 
 
Note! 
For meaning of the error and diagnostic codes, refer to the error list in section Error history. 
When an error has been acknowledged, it can still be read out from the error history.