28/73
Building Technologies Division Basic Documentation LME39… CC1P7106en
8 PC software ACS410 08.12.2017
7.6 Limitation of repetitions (can be
parameterized)
If no flame is established at the end of safety time, or if the flame is lost during
operation, a maximum of 3 repetitions per controlled startup can be performed via
control thermostat/pressurestat, or else lockout will be initiated. Counting of repetitions
is restarted each time a controlled startup via control thermostat/pressurestat takes
place.
Factory setting: No repetition
Note!
In the event of repetition due to loss of flame during operation, a flame signal
must be available at the end of the safety time; if not, the unit will go to lockout.
8 PC software ACS410
8.1 Duty of PC software
The PC software is a component of the LME39… system and serves primarily as an
operator module for the following basic tasks:
Visualization of system state with the following data:
- Parameters
- Process data
Configuration and parameterization of the basic unit (individual parameters)
Reset
For operating and commissioning instructions, refer to Installation and Operating
Instructions J7352.