Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 26 Parameter level 01.12.2009
P
Vh
mi n
s%
Bild 117/070 7
Phase
Traveling to ignition position
Wait until the burner is in operation and symbol ▲ or ▼ is no longer highlighted!
The startup sequence stops in phase 36 Traveling to ignition position.
The ignition position can be adjusted under ”cold” conditions.
F
or A
and
or
as well as
F
and A
and
or
P
Vh
mi n
s%
Bild 118/070 7
Ignition position
P0 can only be set after symbol
▲ or ▼ is no longer highlighted.
For fuel, keep
F depressed, for air, A , as
well as for VDS F and A
Press
or to adjust the value.
As soon as symbol ▲ or ▼ is no longer high-
lighted, the next curvepoint
P1 can be selected
with
.
P
Vh
mi n
s%
Bild 117/070 7
Phase
Traveling to ignition position
P
Vh
mi n
s%
Bild 119/070 7
Phase
Preignition
P
Vh
mi n
s%
Bild 120/070 7
Phase
1st safety time (ignition transformer ON)
P
Vh
mi n
s%
Bild 121/070 7
Phase
1st safety time (ignition transformer OFF),
preignition time OFF
P
Vh
mi n
s%
Bild 122/070 7
Phase
Interval 1