Figure 62: Setting the curvepoints
&
Note
Curvepoints P2 to P8 are automatically computed as a straight line between P1 and P9.
Example 1 = gas modulating
Curvepoint Value 1
fuel
Value 2
air
P0 30.0 22.0
P1 32.0 24.0
P0, P1 and P9 are set as described:
P9
80.0 90.0
P2
through P8 have automatically been
calculated:
Curvepoint Value 1
fuel
Value 2
air
P2 38.0 32.3
P3 44.0 40.5
P4 50.0 48.8
P5 56.0 57
P6 62.0 65.3
P7 68.0 73.5
P8
74.0 81.8