EasyManua.ls Logo

Siemens LOGO! 230 RC - Abbreviations

Siemens LOGO! 230 RC
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LOGO! manual
EWA 4NEB 712 6006-02
106
Criterion ValuesComplies with
Electromagnetic compatibility (EMC)
Electrostatic
discharge
IEC 801-2
Severity 3
8 kV air discharge
6 kV contact discharge
Electromagnetic fields IEC 801-3 Field strength 10V / m
Interference suppression EN 55011 Limit class B group 1
Burst pulses IEC 801-4
Severity 3
2 kV
(supply lines)
2 kV (signal lines)
Energy carriers single
pulse (surge)
(applies only to
LOGO! 230R and
LOGO! 230RC)
IEC 801-5
Severity 2
0.5 kV (supply lines) sym-
metrical
1 kV (supply lines) asym-
metrical
Information on IEC/VDE safety
Measurement of clearance
and creepage distance
IEC 664, IEC 1131,
EN 50178 11/94
UL 508, CSA C22.2
No 142
Also VDE 0631 for
LOGO! 230R/RC
Fulfilled
Insulation strength IEC 1131 Fulfilled
Technical data on LOGO! 230R and LOGO! 230RC
Power supply
Input voltage
Rated value
Permissible range
VDE 0631:
IEC 1131:
Permissible mains frequency
115 V/120 V/230 V/240 V AC
85 V to 250 V AC
85 V to 265 V AC
47 to 63 vHz
Power consumption from
115/120 V AC
230/240 V AC
Voltage failure bridging
115/120 V AC
230/240 V AC
Typically 40 mA
Typically 26 mA
Typically 10 ms
Typically 20 ms
Technical data

Table of Contents