Short circuit-proof
cos 0.5 to 0.7
Power protection B16
900A
Parallel switching of outputs to
increase power
Not permitted
Protection of output relay Maximum 16 A,
Characteristic B16
Switching rate
Mechanical 10 Hz
ohm load/lamp load 2 Hz
Inductive load 0.5 Hz
Technical data of LOGO! 24
Power supply
Input voltage
Rated value
Permissible range
24 V DC
20.4 V to 28.8 V DC
Power consumption from 24 V DC
(with fully loaded outputs)
Typically 1.23 A
Power loss of LOGO! 24 at 24 V DC Typically 0.6 W
Digital inputs
Electrical isolation No
Input voltage 24 V DC
Rated value
At signal 0
At signal 1
24 V DC
<5.0 V DC
>15.0 V DC
Input current at signal 1 Typically 3 mA
Delay time
At 0 after 1
At 1 after 0
Typically 50 ms
Typically 50 ms
Line length (unshielded) 100 m