7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 101
mmmmm
Parameters
Entry:
0 = OFF
1 = alternate display
2 = reset totalizer 1
3 = zero
4 = span
5 = print
6 = multispan selection *
7 = reserved
8 = reset batch
8 reset batch:
momentary closure of the input
contact resets the batch totalizer
to zero.
9PID freeze:
off
closure suspends PID function
in the auto mode
freeze
function in the auto mode
and holds output at last value
10 PID setpoint source:
remote
local
11 PID mode:
auto
manual
12 external alarm:
the input contacts status is
sensed off
13
remote
communication
write:
keypad / Dolphin Plus write (pro-
gram) enabled
SmartLinx®/ remote device write
(program) enabled
14
initiate on-line
calibration:
momentary closure of the input
contact initiates on-line calibra-
tion
15
accept new on-line
calibration span:
momentary closure of the input
contact accepts the on-line cali-
bration deviation
Notes:
• A remote Span performs a zero function, and requires the user to set up a span
test. Once the test weight is within +/-2% of the design test rate, a span is
performed.
• To use the Print command, run the SF 500 in RUN mode.
• Before you can use On-line Calibration, P100,P255, P355, P356, and P357 must be
set up.
Value Function Symbol Description