Page 48 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01
mmmmm
Recalibration
Program the SF 500 as follows:
Parameter Function
P390 = 1 linearization ON
P391-01 = 30 point 1, rate
P391-02 = 60 point 2, rate
P391-03 = 90 point 3, rate
P391-04 = 120 point 4, rate
P391-05 = 150 point 5, rate
P392-01 = - 10.7 point 1, compensation
P392-02 = 11.1 point 2, compensation
P392-03 = - 5.1 point 3, compensation
P392-04 = 8.7 point 4, compensation
P392-05 = -6.0 point 5, compensation
Note: Often only one point of compensation is required, usually at a low rate
value. In the prior example, if compensation was only required at 30 t/h, program
the following parameters. Optimize compensation by establishing the next rate
value that agrees with the material test, the compensation is zero and is entered
as the next compensation point.
P390 = 1 linearization on
P391-01 = 30 point 1, rate
P391-02 = 90 point 2, rate
P392-01 = -10.7 point 1, compensation
P392-02 = 0 point 2, compensation
0
5
10
15
20
25
30
0
12030
-10.7
150 24060 18090 210
Weight = tonnes
actual weight per material test
totalized weight by SF 500
flowmeter response
linearized SF 500 response
internal response 100% - 150% of span
% compensation
span (100%)
rate t/h