Functions
5.1 Connecting other bus systems
PROFINET with STEP 7 V15
116 Function Manual, 12/2017, A5E03444486-AH
Diagnostic options with a CPU S7-1500 as IO controller
The CPU S7-1500 (as of firmware version 1.7) as IO controller detects disrupted DP slaves
behind the IP/PB link.
5.1.3
Connect the DP slave via the IE/PB Link to a PROFINET IO system
Requirements
STEP 7 as of V13 SP1
S7-1500 CPU as of firmware version 1.7
ET 200SP CPU as of firmware version 1.7
CPU 1516pro-2 PN as of firmware version 2.0
S7-1500 Software Controller as of firmware version 1.7
S7-300/400 CPU
Procedure for connecting a DP slave via an IE/PB Link
To connect a DP slave to a PROFINET IO system via an IE/PB Link in STEP 7, follow these
steps:
1. Drag-and-drop a PROFINET CPU, for example CPU 1513-1 PN, from the hardware
catalog into the network view of STEP 7.
2. Drag-and-drop an IE/PB Link PN IO from the hardware catalog into the network view of
STEP 7. The IE/PB Link PN IO is located under Network components > Gateways >
IE/PB Link PN IO.
3. Assign the IE/PB Link PN IO to the CPU.
4. Drag a PROFIBUS interface module e.g. IM155-6 DP HF, from the hardware catalog to
the network view.
5. Assign the interface module to the IE/PB Link.
Figure 5-3 Configuring an IE/PB link
6. Select the IE/PB Link PN IO in the network view of STEP 7.