7.1 Calibrating analog modules
Analog value processing
112 Function Manual, 06/2014, A5E03461439-AC
7.1.4
Resetting analog modules to factory settings
Requirement
You have opened the "Online & Diagnostics" view for the selected analog module from
the shortcut menu of the project and you are now in the "Functions > Calibration" area.
The associated CPU is online.
Procedure
Proceed as follows to reset the channel of an analog module to factory settings:
1. In the overview table, select the line of the channel to be calibrated.
2. Click the "Set to factory settings" button.
Result
The factory settings of the channel are restored.
Note
When you reset the current channel to the factory settings, the original calibration values that
were saved in the delivery state of the module become effective once again. Any existing
user calibration values of this channel are lost. You cannot restore these user calibration
values.