Functions
5.5 Intelligent DP slaves (I-slaves)
PROFIBUS with STEP 7 V13
82 Function Manual, 12/2014, A5E03775446-AC
Data exchange between higher-level DP master and normal DP slave
In this way, the DP master and the DP slave exchange data through PROFIBUS.
Data exchange between higher-level DP master and I-slave
In this way, the DP master and the slave exchange data through PROFIBUS.
The data exchange between a higher-level DP master and an I-slave is based on the
conventional DP master/DP slave relationship.
For the higher-level DP master, the transfer areas of the I-slave represent submodules of a
DP slave.
The output data of the DP master is the input data of the I-slave. Analogously, the input data
of the DP master is the output data of the I-slave.
Transfer relationship between the user program and the transfer area
In this way, the user program and the transfer area exchange input and output data.
Data exchange between the user program and the I/O of the I-slave
In this way, the user program and the centralized I/O of the I-slave exchange input and
output data.
5.5.3
Configuring an I-slave
Requirements for configuring an I-slave
The I-slave consists of:
A CPU from S7-1500 and a communications module CM 1542-5/CP 1542-5
(STEP 7 as of V12)
A CPU from ET 200SP and a communications module CM DP (STEP 7 as of V13 SP1)