System overview
2.6 IODD and Port Configuration Tool - S7-PCT
IO-Link system
Function Manual, 12/2017, A5E31637677-AB
17
2.6
IODD and Port Configuration Tool - S7-PCT
Device description IODD
An electronic device description, the IODD file (IO Device Description) is available for each
device. The IODD provides a wealth of information for system integration:
Communication properties
Device parameters with value range and default value
Identification, process and diagnostic data
Device data
Text description
Image of the device
Manufacturer logo
The structure of the IODD is identical for all devices from all manufacturers. The structure of
the IODD is always represented in the identical manner by the IO-Link Configuration Tool of
the master manufacturer (for Siemens, S7-PCT). This ensures that the handling is the same
for all IO-Link devices regardless of the manufacturer.
Two different IODD versions are available for devices that support both V1.0 and V1.1
functionality.
IODDfinder
The IODDfinder is a cross-vendor, central IO-Link database.
This database provides you with the latest IODDs of the device manufacturers and offers an
information and download platform.
The IODDfinder is available on the Internet (https://ioddfinder.io-link.com
).
IO-Link configuration tool
Configuration tools are required to configure the entire IO-Link system. The IO-Link
configuration tools of the master manufacturers are able to read IODDs.
The main tasks of the IO-Link configuration tool include:
Assigning the devices to the ports of the master
Address assignment of ports within the address area of the master
Assigning parameters for the IO-Link device
Diagnostics can also be carried out on the connected devices.
This means the IO-Link configuration tool supports the transparent representation of the
IO-Link system down to field level.