Integration into the automation system
3.1 Configuration of the IO-Link system
IO-Link system
Function Manual, 12/2017, A5E31637677-AB
25
3.1.2
Configuration without S7-PCT
Introduction
The following sections describe how you configure your IO-Link master without the S7-Port
Configuration Tool (S7-PCT).
Your options for configuration of the IO-Link system without S7-PCT are limited.
You can configure the port of the IO-Link master using STEP 7 or the GSD file, but you
cannot set any parameters of the lower-level IO-Link devices.
Configuration without S7-PCT
You can activate the following parameters in STEP 7 or the GSD file during port
configuration:
Port Qualifier Information (PQI):
provides information on the status, such as process data of the IO-Link port; is
transmitted with the input data of the IO-Link device.
Operating mode
IO-Link Autostart:
The IO-Link master accepts each connected IO-Link device and starts it automatically.
IO-Link Manual:
The IO-Link master only accepts IO-Link devices that match the Vendor ID and Device
ID set below.
The connected IO-Link device is
not
started automatically.
DI:
The port is operating as a standard digital input.
DQ:
The port is operating as a standard digital output.
Disabled:
The port is disabled.
Input Data Length:
Process data length of the input data
Output Data Length:
Process data length of the output data
Vendor ID
ID number of the device manufacturer. You can find the Vendor ID on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109748852
).