Industrial Ethernet Security with CP 1543-1
13.2 Logging
Communication
244 Function Manual, 12/2017, A5E03735815-AF
13.2
Logging
Functionality
For test and monitoring purposes, the security module has diagnostics and logging functions.
Diagnostics functions
These include various system and status functions that you can use in online mode.
Logging functions
This involves the recording of system and security events. Depending on the event type,
the recording is made in volatile or non-volatile local buffer areas of the CP 1543-1. As an
alternative, it is also possible to record on a network server.
The parameter assignment and evaluation of these functions is only possible with a
network connection.
Recording events with logging functions
You specify which events should be recorded with the log settings. Here you can configure
the following recording variants:
Local logging
With this variant, you record the events in local buffers of the CP 1543-1. In the online
dialog of the Security Configuration Tool, you can then access these recordings, visualize
them and archive them on the service station.
Network Syslog
With the network Syslog, you use a Syslog server in the network. This records the events
according to the configuration in the log settings.
13.3
NTP client
Functionality
To check the time validity of a certificate and the time stamp of log entries, the date and time
are maintained on the CP 1543-1 as on the CPU. This time can be synchronized with NTP.
The CP 1543-1 forwards the synchronized time to the CPU via the backplane bus of the
automation system. This way the CPU also receives a synchronized time for the time events
in program execution.
The automatic setting and periodic synchronization of the time takes place either via a
secure or non-secure NTP server. You can assign a maximum of 4 NTP servers to the
CP 1543-1. A mixed configuration of non-secure and secure NTP servers is not possible.