Representation of analog values
3.3 Representation of output ranges
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
63
Representation of output ranges
The tables below set out the digitalized representation of the output ranges by bipolar and
unipolar range. The resolution is 16 bits.
Please see the device manuals for each analog output module for assignment of the values
to the specific output values in each measuring range.
Table 3- 5 Bipolar output ranges
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Maximum output
Over range
Rated range
Under range
-32512 -117.593 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 Minimum output
32511 are specified, the output value is limited to 117.589 % or 0 % (0.0 V / 0.0 mA), depending on the
module used.
-32512 are specified, the output value is limited to -117.593 % or 0 % (0.0 V / 0.0 mA), depending on the