Configuring and parameter assignment
3.3 Configure IO-Link and activate Time-based IO
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
27
Setting for Time-based IO
If you have no special response time requirements, the following setting is suitable as a
starting point:
Send clock: 2 ms
Application cycle: 4 ms
Assignment to the process image partition: PIP1
PIP_Mode: 0 (OIP model)
See also
Programming of Time-based IO (Page 30)
3.3
Configure IO-Link and activate Time-based IO
Introduction
For Time-based IO, the ports of the IO-Link Master must be set to the required operating
mode and suitable sensors/actuators must be connected to the ports.
Requirements
S7-PCT is installed on the programming device/PC.
IODD for IO-Link Device (with time stamp function) are installed.
You can find additional information on installation in the online help for S7-PCT.
The project is open in network view in the TIA Portal.
The hardware catalog is open.