Functions
5.7 Isochronous mode
PROFINET with STEP 7 V15
202 Function Manual, 12/2017, A5E03444486-AH
The "SYNC_PI" and "SYNC_PO" instructions can update the process image partition only
within the permitted execution window. The execution window for the possible call of the
"SYNC_PI" and "SYNC_PO" instructions stretches from the end of the cyclical data
exchange on the PROFINET IO until the point in time before the end of T_DC at which the
outputs can still be copied on time. The data exchange must be started within this time
window. If the "SYNC_PI" and "SYNC_PO" instructions are not processed within the
execution window, the system functions will indicate this with a corresponding error
message. An image in which the execution window and the corresponding times are
displayed can be found in the next section.
Depending on the order of the "SYNC_PI" and "SYNC_PO instructions in OB6x and the
application cycle factor used, the program execution can be divided into two basic models:
●
model (read
nputs -
rocessing - write
utputs), CACF = 1
●
model (read
nputs -
rocessing - write
utputs), CACF > 1
Program processing according to the IPO model with application cycle = 1
Characteristics of the IPO-model with application cycle factor = 1
The IPO model with application cycle factor = 1 is characterized by the fact that the
execution of the I/O data is complete within one system clock cycle T_DC. The shortest
response times are achieved with this model.