Functions
5.2 Intelligent IO devices (I-devices)
PROFINET with STEP 7 V15
128 Function Manual, 12/2017, A5E03444486-AH
Requirements
You have configured an I-device.
Task
The result of an "AND logic operation" of two inputs (preprocessing) in the I-device is to be
provided to the higher-level IO controller. This result is to be assigned to a local output in the
IO master (further processing).
Use a transfer area with the following addresses for this purpose:
Address in the I-device: Q568
Address in the IO controller: I68
Required steps
The following steps to solve the task:
1. Configuring the transfer area
2. Programming I-device
3. Programming IO controller
Configuring the transfer area
Configure a transfer area with the following properties in the I-device:
Figure 5-14 I-device transfer area, sample program