5.3 Shared device
PROFINET with STEP 7 V15
160 Function Manual, 12/2017, A5E03444486-AH
3. Place the I/O modules from the hardware catalog in a suitable slot.
4. Add MSI/MSO submodules to the I/O modules:
Input modules: Select the number of MSI submodules under "Module parameters
" > "DI configuration" or "AI configuration" in the area "Copy of module for Shared
Device (MSI)".
Output modules: Select the number of MSO submodules under "Module parameters
" > "DQ configuration" or "AW configuration" in the area "Copy of module for shared
device (MSO)".
Figure 5-32 Configuring I/O modules with MSI/MSO
Assigning MSI/MSO submodules to an IO controller
You can assign the submodules in a shared device to an IO controller.
For more information, refer to Configuring shared device (Page 141).
Configuring access to a shared device and the module-internal shared input / shared output
(MSI /MSO) function
You can learn how to access a shared device and the MSI /MSO function in STEP 7 with this
FAQ (https://support.industry.siemens.com/cs/ww/en/view/109736536
).