5.6 PROFINET with performance upgrade
PROFINET with STEP 7 V15
196 Function Manual, 12/2017, A5E03444486-AH
3. Select the option "Cable length" or "Signal delay:".
4. Select the cable length or enter the signal delay.
Figure 5-62 Optimizing port settings for low send clocks
Allowing fast forwarding
Requirements:
The PROFINET IO device has to support the fast forwarding process so that the process
can be used by the device.
The "Make 'high performance' possible" option is enabled.
The PROFINET IO interface supports fast forwarding if all the ports except one are
deactivated.
Follow these steps to allow fast forwarding:
1. Select the PROFINET IO system in the network view of STEP 7.
2. In the Inspector window, go to "Properties" > "General" > "PROFINET" > "Domain
management" > "Sync domains" > "Name of the sync domain".
3. Enable the "Allows the use of ‘fast forwarding'" option.
Figure 5-63 Allowing fast forwarding