EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 1166

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.9 Standard machine projects
PROFINET with STEP 7 V15
Function Manual, 12/2017, A5E03444486-AH
219
The following figure shows how an automation solution with a multiple use IO system is
loaded on different automation systems and then one automation system is adapted to the
existing network infrastructure locally.
Load configuration with multiple use IO system
Set IP address and device name locally on the IO controller
Figure 5-76 "Multiple use IO system" principle
Principle
The automation components for a machine include a PROFINET IO system, consisting of an
IO controller (PROFINET interface of a CPU) and the IO devices assigned to it.
With the "Multiple use IO system" setting for the IO system, you turn a STEP 7 project into a
"Standard machine project".
The "Multiple use IO system" setting triggers various settings and checks of the configuration
by STEP 7. The settings ensure that the IO system is self-contained and there are no
dependencies on components outside the IO system.
Requirements
STEP 7 as of V13
The IO controller supports the "Multiple use IO system" function, for example a CPU
1512SP-1 PN as of firmware version 1.6.

Table of Contents

Other manuals for Siemens SIMATIC ET 200AL

Related product manuals