2.2 Structure of PROFIBUS networks
PROFIBUS with STEP 7 V13
18 Function Manual, 12/2014, A5E03775446-AC
Selection criteria for networking
The table below includes selection criteria for electrical and optical networking of PROFIBUS
devices:
Table 2- 3 Selection criteria for electrical and optical networking
Criteria
Electrical
PROFIBUS
Optical network
with OLM
Optical network
with OBT
Transmission
medium
Shielded two-wire
line
POF
PCF
Glass
Distances
Max. network span PROFIBUS DP:
9.6 km
PROFIBUS PA:
1.9 km
90 km 9.6 km
Between two devices up to 1 km
1)
up to 15 km
2)
up to 300 m
2)
Topology
Bus
Linear
Tree
Ring
Transmission
protocols
DP, PA DP, PA DP
Connection of
devices by means
of
OLM
Integrated interfaces
Bus terminal
Bus connector
Electrical network
segments can be
connected
● Suitable
Not relevant for this application
1) Depending on data rate and type of service used
2) Depending on cable type used
Installation guideline for PROFIBUS networks
A PROFIBUS segment must be terminated at the start and end; passively with a connector
or actively with a bus terminating resistor.
The same principles apply to the installation of a PROFIBUS network as described in the
SIMATIC NET PROFIBUS networks
(http://support.automation.siemens.com/WW/view/en/35222591) manual.