EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 1415

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
What you should know about analog technology
2.20 Burden with 2-wire transducers
Analog value processing
58 Function Manual, 06/2014, A5E03461439-AC
Example 1: Connecting a transducer to the electrical circuit
In accordance with the technical data of the 2-wire transducer used, it requires a supply
voltage (U
min
) of at least 8.5 V. Using Ohm's Law, you can calculate the resistance of the
transducer used (R
2DMU
) for a current of 20 mA.
With a supply voltage of at least 8.5 V, the transducer has a resistance of 425 Ω. The
resistance is less than 820 Ω. You can therefore connect the transducer to the analog input
module (AI) without exceeding the maximum burden.
2-wire transducers
U
V
Terminal for feed voltage at the channel
I+
Terminal for current input
U
min
Voltage drop at 2-wire transducer
Figure 2-27 Connecting a transducer to the electrical circuit