What you should know about analog technology
2.20 Burden with 2-wire transducers
Analog value processing
58 Function Manual, 06/2014, A5E03461439-AC
Example 1: Connecting a transducer to the electrical circuit
In accordance with the technical data of the 2-wire transducer used, it requires a supply
voltage (U
min
) of at least 8.5 V. Using Ohm's Law, you can calculate the resistance of the
transducer used (R
2DMU
) for a current of 20 mA.
With a supply voltage of at least 8.5 V, the transducer has a resistance of 425 Ω. The
resistance is less than 820 Ω. You can therefore connect the transducer to the analog input
module (AI) without exceeding the maximum burden.
Terminal for feed voltage at the channel
Terminal for current input
Voltage drop at 2-wire transducer
Figure 2-27 Connecting a transducer to the electrical circuit