BusAdapter BA-Send 1xFC
6.5 Technical specifications
Product Information Mixed Configuration ET 200SP / ET 200AL
24 Product Information, 02/2016, A5E33344611-AC
DIAG LED
Table 6- 2 Status and fault display DIAG
DIAG LED
Meaning
Remedy
Off
There is no connection between the
ET-Connection interface of the
BusAdapter BA-Send 1xFC and ET
200AL.
Check whether the bus cable is interrupted.
The interface module does not sup-
port the BA-Send 1xFC.
Run a firmware update.
On
There is a connection between the
ET-Connection interface of the
BusAdapter BA-Send 1xFC and ET
200AL.
---
Flashes
There is (at least) one diagnostics
alarm of an ET-Connection device.
Group error for all ET-Connection
bus nodes.
Check the ET-Connection device.
Set configuration does not match the
actual configuration on the ET-
Connection.
Check the configuration of the ET-Connection to see
whether a module is missing or defective, or whether a
non-configured module is wired.
6.5
Technical specifications
Technical specifications of the BusAdapter BA-Send 1xFC
6ES7193-6AS00-0AA0
Interfaces
PROFINET IO
Cable length
Copper cables
15 m; as of IM firmware V3.3: Bus nodes be-
tween BA-Send and the first ET-Connection as
well as between all other bus nodes.
ET-Connection
Number of interfaces ET-Connection
1
FC (FastConnect)
Yes
Ambient conditions
Ambient temperature in operation
Min.
0 °C
Max.
60 °C
Dimensions
Width
20 mm
Weights
Weight, approx.
44 g