6.2 Wiring loads/actuators
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
105
Reference potential for analog output modules without M
ANA
connection
Analog output modules have no galvanic connection between the reference potential of the
analog output circuits and central ground.
Always verify that the maximum potential difference U
ISO
between the reference points of the
analog output circuits and the central ground is not exceeded.
Potential difference U
ISO
may be caused by: Maximum line lengths exceeded.
If you want to ensure the maximum value U
ISO
is not exceeded, interconnect each analog
output circuit with the central ground using an equipotential bonding cable.
Load on the voltage output
Equipotential bonding cable
Grounding bus cable
Central ground
Figure 6-2 Example: Reference potential for an analog output module without M
ANA
connection