Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
39
The table below shows the parameters of the TIO_IOLink_IN instruction.
Hardware identifier for TIO module from HWCN
Port number (1 to 4) of the connected IO-Link Device
TIO_SYNC_
Data*
Input "TIO_SYNC_
Data"
System time provided for the TIO instructions of the TIO
modules by the TIO_SYNC instruction. See UDT
"TIO_SYNC_Data" (Page 57).
Connect this input parameter with the "TIO_SYNC_Data" output
parameter of the TIO_SYNC instruction.
TO* Input LTime LT#0ns T
o
: Time for output of isochronous output data.
Apply T
o
from the ET 200 station (properties of the PROFINET
SA_Bit0 Output Bool False Display of a process data change (bit 0 of SA_Data).
SA_Bit0 is event-oriented. As long as no valid time stamp has
been acquired (EventCount = 0), the process data are invalid.
SA_Bit1 Output Bool False Display of a process data change (bit 1 of SA_Data).
SA_Bit1 is event-oriented. As long as no valid time stamp has
been acquired (EventCount = 0), the process data are invalid.
Process data SA_Data (Sensor Application Data)
TimeStamp Output LTime LT#0ns Time stamp: Time when a change of the process signal SA-
Data took place at the IO-Link Device.
EventCount Output UInt 0 Counter: Is incremented with each new, valid time stamp. The
counter is reset with each CPU startup.
Status of the instruction: see description of Status parameter
Error Output Bool False If True, this output indicates that an error has occurred. For
detailed information see Status parameter.
Error is reset as soon as the error is remedied.
* Checked once at startup of the CPU