Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
51
10070000 An internal error occurred during the address calculation. Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO
module from its module properties in HWCN.
An internal system constant of data type
Hw_SubModule is available for the symbolic
00080000 TIO module is not synchronized using the TIO_SYNC
Check the instruction TIO_SYNC.
10090000 The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
APP
<= 16 ms and is therefore
invalid.
The instruction can only be used without errors in an
• Correct the cycle time.
• Make sure that TIO_IOLink_OUT is called in
a "Synchronous Cycle" OB.
100A0000 The assigned time at the TO input parameter is outside
the permitted range of 0 < T
o
Correct the value at the TO input parameter.
100Bxxxx An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from RD_ADDR.
Read the description of the RD_ADDR in the
TIA Portal information system.
000C0000 The time stamp at the TimeStamp input parameter is
invalid.
Check the TimeStamp input parameter.
000D0000 The value status PortQualifier of the IO-Link indicates that
the process data is invalid.
Check the connected sensor and its
100E0000 The configured port mode of the IO-Link is incorrect. Check the configuration of the connected
100F0000 The read cycle time of the "Synchronous Cycle" OB is too
APP
Configure a smaller multiple of the send clock