Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
56 Function Manual, 08/2014, A5E33454822-AB
Error code
Meaning
Remedy
(DW#16#...)
10070000 An internal error occurred during the address calculation. Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO
module from its module properties in HWCN.
An internal system constant of data type
Hw_SubModule is available for the symbolic
addressing.
x0080000 TIO module is not synchronized using the TIO_SYNC
instruction.
The error code can also indicate that:
A job was already present before the first run of the
instruction.
The assigned number at the Channel input parameter
is not a digital output.
Check the instruction TIO_SYNC.
10090000 The read cycle time of the isochronous OB is LT#0ms or
has as negative value and is therefore invalid. Correct the
value.
The instruction can only be used without errors in an
isochronous OB.
Correct the cycle time.
Make sure that TIO_DQ is called in a
"Synchronous Cycle" OB.
100A0000 The assigned time at the TO input parameter is outside
the permitted range of 0 < T
o
<= 4 ms.
Correct the value at the TO input parameter.
100Bxxxx An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from RD_ADDR.
Read the description of the RD_ADDR in the
TIA Portal information system.
000C0000 One or both time stamps at the TimeStampRE and
TimeStampFE input parameters are invalid. The error is
only signaled for the duration of one application cycle.
Check the TimeStampRE and TimeStampFE
input parameters.
000D0000 The Quality Information of the digital output indicates that
an error has occurred at the digital output.
Check the parameter assignment of the
digital output.
Check the wiring of the digital output for
short-circuit, overload, and overtemperature.
000E0000 The assigned number at the Channel input parameter is
not a digital output.
Check the channel configuration (only for
TM Timer DIDQ 16x24V).
Check the operating mode of the digital
output.
100F0000 The read cycle time of the "Synchronous Cycle" OB is too
long. T
APP
> 16 ms.
Configure a smaller multiple of the send clock
as the cycle time.
10100000 The send clock is outside the permitted range of 0 <
SEND_CLOCK <= 4 ms and is therefore invalid.
The error code can also indicate that
The data in TIO_SYNC_Data is invalid or does not
exist.
The TIO_DQ instruction is not called in an isochronous
OB.
Correct the send clock.