Interference-free cable routing
3.1 Classifying cables into cable categories
Designing interference-free controllers
10 Function Manual, 06/2014, A5E03461486-AB
The following table shows the minimum clearance you must maintain when installing cables.
Table 3- 2 Combination of cable categories
Category A
Category B
Category C
Category A
In common bundles
or cable channels
In separate bundles
or cable channels
(no minimum
clearance
necessary)
Inside cabinets in separate
bundles or cable channels
Outside cabinets, but inside
buildings, on separate cable
racks with at least 10 cm
clearance
Category B
In separate bundles
or cable channels
(no minimum
clearance
necessary)
In common bundles
or cable channels
Category C
Inside cabinets in separate bundles or cable
channels
Outside cabinets, but inside buildings, on
separate cable racks with at least 10 cm
clearance
In common bundles or cable
channels
If you install different cable categories in the same cable channel, use metallic cable
channels with metallic partition.
The following figure show a schematic view of a cable channel with partition.
Metallic cable channel
Metallic partition
Figure 3-1 Cable channel with partition