EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 185

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interface module IM 157-1 DP (6ES7157-1AA00-0AB0)
42 Manual, 12/2016, A5E32100641-AD
Technical specifications
6
Technical specifications of the interface module IM 157-1 DP
6ES7157-1AA00-0AB0
General information
Product type designation
IM 157-1 DP
Hardware functional status
E01
Firmware version
V1.0.x
Vendor identifier (VendorID)
81A9H
Product function
I&M data
Yes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal can be configured/integrated
as of version
as of STEP 7 V13 SP1
STEP 7 can be configured/integrated as of version
V5.5 SP4 Hotfix 3 or higher
PROFIBUS as of GSD version/GSD revision
GSD as of revision 5
Configuration control
Via data record
Yes
Supply voltage
Load voltage 1L+
Rated value (DC)
24 V
Low limit of permitted range (DC)
20.4 V
High limit of permitted range (DC)
28.8 V
Reverse polarity protection
Yes; against destruction
Input current
Current consumption (rated value)
50 mA
From load voltage 1L+ (unswitched current)
4 A; maximum value
From load voltage 2L+, max.
4 A; maximum value
Power loss
Power loss, typ.
1.7 W
Address area
Address space per station
Address space per station, max.
244 bytes
Interfaces
Number of PROFIBUS interfaces
1
1st interface
Interface type
PROFIBUS DP