Product overview
2.3 Functions
Interface module IM 157-1 PN (6ES7157-1AB00-0AB0)
Manual, 12/2016, A5E32347036-AD
19
Parameter data record
You specify in the parameter data record for PROFIenergy which I/O modules (slots) are
controlled with the PROFIenergy commands.
The following table shows the content of the parameter data record for PROFIenergy, index
3, which you create yourself and can transfer to the interface module.
Table 2- 3 Parameter data record for PROFIenergy (version 2), index 3
Byte
Element
Code
Explanation
0
Version
02
D
Cannot be modified
1 Number of blocks 01
D
to 34
D
Slots 1 to 34 depending on the configuration of
the distributed I/O system ET 200AL
2 Block 1 Slot num-
ber
00
D
Not assigned
01
D
to 34
D
I/O module slot with PROFIenergy
3 Mode 0
D
: PE_MODE_PROCEED, proceed at "Pause"
1
D
: PE_MODE_SHUTDOWN, shut down at "Pause"
1
3
D
: PE_MODE_LAST_VALUE, last output or measured value is
retained
4
D
: PE_MODE_SUBST_VALUE, substitute value "0"
2
:
:
:
:
64 Block 32 Slot num-
ber
See Block 1
65
Mode
1
The specific behavior depends on the used I/O module (with a digital input module, for example,
the sensor supply is turned off or the outputs are without power supply and voltage supply with an
analog output module)
2
An analog output module (e. g. with the output range 0 mA to 20 mA, ± 20 mA) or a digital output
module issues the value "0".
Error messages
The following table shows which error messages the feedback data record returns, if
necessary:
Table 2- 4 Error messages
Error code
Meaning
80B1
H
Impermissible length
Check the length of the data record
80E0
H
Error in header information
Check the data record header information
80E1
H
Parameter error
at least one I/O module does
not support PROFIenergy
A parameter value has been
incorrectly encoded
Check the co
ntent of the data record and correct the
parameter assignment error before starting the
"Pause". Parameter assignment errors which are
not corrected can result in incorrect I/O module
shutdown behavior.