EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 216

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interrupts, error messages, diagnostics and system alarms
5.1 Status and error displays
Interface module IM 157-1 PN (6ES7157-1AB00-0AB0)
Manual, 12/2016, A5E32347036-AD
27
Meaning of the LEDs
The following tables set out the meaning of the status and error displays. Corrective
measures for diagnostics alarms can be found in the section Diagnostics alarms (Page 30).
LED RUN, LED ERROR, LED MAINT
Table 5- 1 Status and error displays of the LEDs RUN, ERROR, MAINT
LEDs
Meaning
Solution
RUN
ERROR
MAINT
Off
Off
Off
Missing or insufficient supply voltage on
interface module.
Check the supply voltage or switch it on
on the interface module.
On
On
On
Test of LEDs during startup: The three
LEDs light up simultaneously for approx-
imately 0.25 s.
---
Flashes
Off
Off
Interface module is deactivated.
Activate the interface module with the
configuration software or the user pro-
gram.
Interface module is not configured. Configure the interface module with the
configuration software.
ET 200AL starts up.
---
ET 200AL is being assigned parameters.
On
Not rele-
vant
Not rele-
vant
ET 200AL is currently exchanging data
with the IO controller.
---
Not rele-
vant
Flashes
Not rele-
vant
Group error Evaluate the diagnostics and eliminate
the error.
The preset configuration does not corre-
spond to the actual configuration of the
ET 200AL.
Check the configuration of the ET 200AL
to see whether a module is missing, de-
fective or if a module that is not config-
ured is connected to ET-CON1 or
ET-CON2 .
Parameter assignment error in the I/O
module
Evaluate the display of the module status
in STEP 7 or in STEP 7 (TIA portal) and
correct the errors in the I/O module.
Not rele-
vant
Not rele-
vant
On
Maintenance See section Maintenance events
(Page 32)
Flashes
Flashes
Flashes
The "Node flash test" is run (the LEDs
P1 LINK and P2 LINK of the PROFINET
interface also flash).
---
Hardware or firmware defective (The
LEDs P1 LINK and P2 LINK of the
PROFINET interface do not flash).
Replace the interface module.
Flashes
Not rele-
vant
Not rele-
vant
Firmware is loading
(all LEDs remain in their current state
while the firmware update is being writ-
ten)
---

Table of Contents

Other manuals for Siemens SIMATIC ET 200AL

Related product manuals