EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 757

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Open User Communication
6.3 Instructions for Open User Communication
Communication
Function Manual, 12/2017, A5E03735815-AF
71
The following table shows you the different connections of the Secure Open User
Communication and the matching system data types and instructions.
Secure OUC connection
System data type
Instructions
Secure TCP connection from an
S7-1500 CPU as TLS client to a
third-party PLC (TLS server)
Secure TCP connection from an
S7-1500 CPU as TLS server to a
third-party PLC (TLS client)
TCON_QDN_SEC TSEND_C/TRCV_C
TCON
Secure TCP connection between
two S7-1500 stations
TCON_IP_V4_SEC
1
Secure connection to a mail serv-
er
2
TMAIL_V4_SEC
TMAIL_QDN_SEC
TMAIL_C (V5.0 or higher)
Secure Modbus TCP connection
TCON_IP_V4_SEC
1
MB_Client
MB_Server
TCON_QDN_SEC
1
Also possible for CP 1543-1
2
Secure connection to a mail server also possible with CP1543-1 und TMAIL_C (V4.0)
Setting up the connection with connection configuration
When setting up through the configuration of the connection, the address parameters of the
connection are specified in the hardware and network editor of STEP 7.
To send and receive the data, use the same instructions as when the connections are set up
by programming:
Table 6- 4 Instructions for sending/receiving with configured connections
Protocol
Send/receive with configured connections
Supported instructions:
TCP
Send/receive data via:
TSEND_C/TRCV_C or
TSEND/TRCV or
TUSEND/TURCV
ISO-on-TCP
ISO according to ISO/IEC 8073
(Class 4)
UDP Send/receive data via:
TSEND_C/TRCV_C or
TUSEND/TURCV
FDL Send/receive data via:
TSEND_C/TRCV_C or
TSEND/TRCV or
TUSEND/TURCV
Modbus TCP
Not supported
E-mail
Not supported
FTP
Not supported