Open User Communication
6.7 Setting up communication with Modbus TCP
Communication
86 Function Manual, 12/2017, A5E03735815-AF
4. Assign the parameters of the MB_CLIENT or MB_SERVER instruction. Observe the
following rules:
An IPv4 server address must be specified for each MB_CLIENT connection.
Each MB_CLIENT or MB_SERVER connection must use a unique instance DB with one
of the data structures TCON_IP_v4 or TCON_QDN.
Each connection requires a unique connection ID. The connection ID and instance DB
belong together in pairs and must be unique for each connection.
Figure 6-9 MB_CLIENT
Figure 6-10 MB_SERVER
5. Download the hardware configuration and user program to the CPU.