EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 825

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPC UA communication
9.1 What you need to know about OPC UA
Communication
Function Manual, 12/2017, A5E03735815-AF
139
The following figure shows the "UA Sample Client" of the OPC Foundation.
The client has established a secure connection to the OPC UA server of an S7-1500 CPU to
the endpoint "opc.tcp://192.168.178.151:4840 - [SignAndEndCrypt: Basic128Rsa15:Binary]".
The security settings "SignAndEndCrypt:Basic128Rsa15" are contained in the endpoint.
Note
Select an endpoint with as strict as possible a security policy
Select an application
-appropriate security policy for the end point and disable the less strict
security policy at the OPC UA server.
A Sha256 certificate
is required for the two most secure end points (Basic256Sha256) of the
S7
-1500 CPU OPC UA server.
Figure 9-4 "UA Sample Client" program of the OPC Foundation
A connection to a server end point is only established if the OPC UA client complies with the
security policies of that end point.

Table of Contents

Other manuals for Siemens SIMATIC ET 200AL

Related product manuals