EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 897

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 12/2017, A5E03735815-AF
211
Recommendation
To minimize risks in the case of an extension or adaptation of the server address space,
follow these steps:
1. Protect the project (project navigation: Security settings > Settings).
2. Export the corresponding server interface before the extension or adaptation.
3. Revise this OPC UA XML file.
4. Import the file again as a server interface.
Mapping data types
The table below shows the compatible SIMATIC data type for each OPC UA data type.
Assign the data types as shown below (SIMATIC data type OPC UA data type). Other
assignments are not permitted. STEP 7 does not check the observance of this rule and does
not prevent an incorrect assignment. You are responsible for the rule-compliant selection
and assignment of the data types.
You can also use the listed data types, for example, as elements of structures/UDTs for input
and output parameters of self-created server methods (UAMethod_InParameters and
UAMethod_OutParameters).
Table 9- 10 Mapping of data types
SIMATIC data type
OPC UA data type
BOOL
Boolean
SINT SByte
INT
Int16
DINT
Int32
LINT
Int64
USINT
Byte
UINT
UInt16
UDINT
UInt32
ULINT
UInt64
REAL
Float
LREAL
Double
LDT
DateTime
WSTRING
String
DINT
Enumeration (Encoding Int32) and all derived data types
User-defined data type required (UDT,
user-defined data type)
The user-defined data type must be
created with the prefix "Union_", for ex-
ample "Union_MyDatatype"; see exam-
ple below table.
The first element (Selector) in this UDT
must have the data type "UDINT".
UNION and all derived data types

Table of Contents

Other manuals for Siemens SIMATIC ET 200AL

Related product manuals