EasyManuals Logo

Siemens simatic ET 200MP Equipment Manual

Siemens simatic ET 200MP
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Product overview
3.3 Functions
Interface module IM 155-5 MF HF (6ES7155-5MU00-0CN0)
30 Equipment Manual, 11/2023, A5E53268530-AA
3.3.3 System redundancy on S7-400H
Connection to H-CPUs with system redundancy
When system redundancy is used, you can connect the IM 155-5 MF HF (6ES7155-5MU00-
0CN0) interface module to CPUs 41x-5H PN/DP (version 6.0 or higher) of the S7-400.
These CPUs allow you to operate the interface module as a component of a redundant
system.
Requirements for the IM 155-5 MF HF interface module:
With STEP 7 V5.5 SP3 and higher, the IM 155-5 MF HF is configured as a system
redundancy device.
The connection setting (transmission medium/duplex) must be set to "Full duplex".
You can find examples for system redundancy in the Fault-tolerant systems S7-400H
(http://support.automation.siemens.com/WW/view/en/60458386) manual.
Combination of system redundancy and Shared Device
The IM 155-5 MF HF interface module can be connected to up to four IO controllers but only
to one H-CPU pair. As a result, a combination of system redundancy and Shared Device
operation is not possible when redundancy operation is used exclusively.
However, you can operate some of the I/O modules of the interface module in system
redundancy on the H-CPU pair and the other I/O modules with up to two additional IO
controllers in Shared Device operation.

Table of Contents

Other manuals for Siemens simatic ET 200MP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic ET 200MP and is the answer not in the manual?

Siemens simatic ET 200MP Specifications

General IconGeneral
BrandSiemens
Modelsimatic ET 200MP
CategoryI/O Systems
LanguageEnglish

Related product manuals