Parameter
5.3 Configuration control (option handling)
Interface module IM 155-5 MF HF (6ES7155-5MU00-0CN0)
Equipment Manual, 11/2023, A5E53268530-AA
45
Data record of the example
The following table shows the structure of the control data record for the above example.
Table 5- 10 Data record for example "Combining configurations"
Byte Element Code configura-
tion 1
Code configura-
tion 2
Explanation
0
Block
length
17
Header
1
Block ID
196
2
Version
3
3
Version
0
4
Slot 0
00000000B
00000000B
The configured slot 0 is the real slot 0.
5
Slot 2
00000010B
00000010B
The configured slot 2 is the real slot 2.
6
Slot 3
00000011B
00000011B
The configured slot 3 is the real slot 3.
7
Slot 4
00000100B
00000100B
The configured slot 4 is the real slot 4.
8
Slot 5
00000101B
00000101B
The configured slot 5 is the real slot 5.
9
Slot 6
01111111
B
00000110
B
The configured slot 6 does not exist (configuration 1).
The configured slot 6 is the real slot 6 (configuration 2).
10
Slot 7
01111111
B
00000111
B
The configured slot 7 does not exist (configuration 1).
The configured slot 7 is the real slot 7 (configuration 2).
11 Slot 8 00000110B 00001000B The configured slot 8 is the real slot 6 (configuration 1).
The configured slot 8 is the real slot 8 (configuration 2).
12 Slot 9 00000111B 00001001B The configured slot 9 is the real slot 7 (configuration 1).
The configured slot 9 is the real slot 9 (configuration 2).
13
Slot 10
00001000
B
00001010
B
The configured slot 10 is the real slot 8 (configuration 1).
The configured slot 10 is the real slot 10 (configuration 2).
14
Slot 11
01111111
B
00001100
B
The configured slot 11 does not exist (configuration 1).
The configured slot 11 is the real slot 12 (configuration 2).
15
Slot 12
01111111
B
00001101
B
The configured slot 12 does not exist (configuration 1).
The configured slot 12 is the real slot 13 (configuration 2).
16
Slot 13
00001001
B
00001011
B
The configured slot 13 is the real slot 9 (configuration 1).
The configured slot 13 is the real slot 11 (configuration 2).