Product overview
2.1 Properties
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
14 Manual, 08/2018, A5E41448857-AB
Supports the "RIOforFA-Safety" profile on F-CPUs S7-1200/1500.
PROFIsafe address type 2
4 analog inputs with electrical isolation between channels and the backplane bus (up to
SIL3/Cat.4/PLd)
Measuring ranges: 0..20 mA and 4..20 mA
Resolution: 16 bits including sign
Short circuit-proof power supply for 2-wire or 4-wire transmitter
Supply voltage L+
External sensor supply possible
Assignable diagnostics
Diagnostics display (DIAG, red/green LED)
Status display for each input (green LED)
Error display for each input (red LED)
Diagnostics
e.g., short-circuit, channel-specific
e.g. supply voltage missing, module-specific
Channel- and module-wide passivation
The module supports the following functions:
Firmware update
I&M identification data
Value status
WARNING
The fail-safe performance characteristics in the technical specifications apply for a mission
time life of 20 years and a repair time of 100 hours. If a repair within 100 hours is not
possible, remove the respective module from the BaseUnit or switch off its supply voltage
before 100 hours expires.
The module switches off independently after the 100 hours have expired.
Follow the repair procedure described in section Diagnostic messages (Page 58).
Note
Cyclic reading of I&M data
Cyclic reading of I&M data can affect the ti
ming of the F-modules. You should therefore
avoid short read cycles of less than 500
ms.