Interrupts/diagnostic messages
6.2 Interrupts
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
56 Manual, 08/2018, A5E41448857-AB
6.2
Interrupts
Introduction
The fail-safe analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF supports diagnostic
interrupts.
Diagnostic interrupt
The F-module generates a diagnostic interrupt for each diagnostic message described in
section Diagnostic messages (Page 58).
The list below provides an overview of the diagnostic interrupts of the F-module. The
diagnostic interrupts are assigned either to one channel or the entire F-module.
WARNING
Before acknowledging the short circuit diagnostic message, remedy the respective fault and
validate your safety function. Follow the fault remedying procedure described in section
Diagnostic messages (Page 58)
Scope of diagnostic interrupt: F-module
Overtemperature
Parameter error
Supply voltage missing
Channel/component temporarily not available
Mismatch of safety destination address (F_Dest_Add)
Safety destination address not valid (F_Dest_Add)
Safety source address not valid (F_Source_Add)
Safety watchdog timer value is 0 ms (F_WD_Time)
Parameter F_SIL exceeds SIL from specific device application
Parameter F_CRC_Length does not match the generated values
Version of F-parameter set incorrectly
CRC1 fault
Inconsistent iParameters (iParCRC error)
F_Block_ID not supported
Transmission error: Inconsistent data (CRC error)
Transmission error: Timeout (monitoring time 1 or 2 expired)
Module is defective
Watchdog tripped
Invalid/inconsistent firmware present