Applications of the F-I/O module   
5.4 Application 4: Safety mode SIL3/Cat.4/PLe with 4-wire transducer 
  Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1) 
52  Manual, 08/2018, A5E41448857-AB 
Assignable parameters for application 4 
Table 5- 4  Parameters for application 4 of F-AI 4xI 0(4)..20mA 2-/4-wire HF 
Range of values in safety mode 
Standard value 
•  MIN 
•  MAX 
Tolerance window %, absolute 
Tolerance window %, relative  2.0 to 20.0% 
Behavior after channel faults 
•  Passivate the entire F-module 
•  Passivate channel 
Interference frequency suppression 
•  50 Hz 
•  60 Hz 
1oo2 evaluation (max. SIL3/Cat.4/PLe) 
Measuring range 
•  0 to 20 mA 
•  4 to 20 mA 
Diagnostics: Wire break  (in the measuring range 4 to 20 mA) 
•  Disable 
•  Enable 
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles