Article number 6DL1134-6UD00-0PK0
General information
Product type designation AI 4xI 2-/4-wire HART ISOL HA
Firmware version V1.0
• FW update possible
Yes
Usable terminal block TB type K0 and L0
Color code for module-specic color identica‐
tion plate
CC40
Product function
• I&M data
Yes; I&M0 to I&M3
Engineering with
• PROFIBUS from GSD version/GSD revision
Yes / Yes
• PROFINET from GSD version/GSD revision
Yes / Yes
Redundancy
• Redundancy capability
Yes; With TB type L0
CiR - Conguration in RUN
Reparameterization possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 75 mA; sensor supply without loads
Current consumption, max. 190 mA; at 1.5 kOhm load on sensor supply
Encoder supply
Number of outputs 4
Output voltage (DC) 24 V
Output voltage, min. 19.2 V
Short-circuit protection Yes; Electronic
Output current
• Rated value
20 mA
• permissible range, lower limit
0 mA
• permissible range, upper limit
23.52 mA
24 V encoder supply
• 24 V
Yes
• Short-circuit protection
Yes
• Output current per channel, max.
23.5 mA
• Output current per module, max.
88 mA
Power loss
Power loss, typ. 1.8 W
Address area
Address space per module
Technical specications
8.1 Technical specications
AI 4xI 2-/4-wire HART ISOL HA
52 Equipment Manual, 07/2022, A5E50101523-AB