Commissioning a project 
  7.4 Transferring a project with WinCC 
Mobile Panels 2nd Generation 
Operating Instructions, 09/2018, A5E33876626-AC 
191 
 
Transferring a project with WinCC 
7.4.1
 
Configuring data channel and setting transfer mode 
Requirement 
●  The project on the HMI device is complete. 
1.  Proceed as described in the section "Configuring transfer (Page 109)". 
2.  Set the operating mode "Transfer" in the "Start Center". 
 
For a project to run on the HMI device, the project must be transferred to the HMI device 
from the configuration PC. With a transfer, you particularly specify whether to overwrite 
existing data on the HMI device such as "User management" or "Recipe data". 
 
  You can transfer a single project using the configuration software or using Pack&Go . On 
HMI devices with an HMI device image that is compatible with WinCC (TIA Portal) V14 or 
higher, you can also transfer an individual project using an external storage medium. 
  With automatic transfer, the HMI device only switches to "Transfer" mode automatically if 
the project is running on the HMI device. 
  If automatic transfer is activated on the HMI device and a transfer is initiated on the 
configuration PC, the project currently running is automatically closed. 
Automatic transfer is particularly suited for the test phase of a new project because transfer 
is remote controlled. When automatic transfer is activated, the HMI device automatically 
switches to "Transfer" mode as soon as a project transfer is started on a connected 
configuration PC.