The SIPART PS2 has been configured with the EDD for SW revision 5.00.00. The PDM
device identification function detects the connected device with deviating SW revision of
4.00.00. A project-specific device overview makes clear how the EDD versions and the
SW/FW revisions of the device relate to one another.
Device
GSD name
EDD name
DD version
DD_Revision
Software
revi-
sion/device
Com
type
SIPART PS2
SI028079.GSD
SIPA_ACP_PS2A_M.DDL
21.768.6-004
6
4.00.00
PA
SIPART PS2 SI028079.GSD SIPA_ACP_PS2A_P.DDL 21.769.1-009 7 5.00.00 PA
6.4
Updating SIMATIC PDM
Applications
For an update of the PCS 7 ES, the SIMATIC PDM version released for this PCS 7 ES and
the associated device catalog should be installed. You can find additional information in the
"PCS 7 Readme (Online)" (https://support.industry.siemens.com/cs/ww/en/view/109744312).
Note
Please note the installation requirements when using a m
ore recent PDM version. You can
find more detailed information in the "PDM Readme" ("pdmbase
-readme") on your SIMATIC
PDM CD.
Note
The PDM version and device descriptions must match on all PCS 7 ES on which the PDM
project is edited.