Firmware update of hardware
5.5 Updating firmware of a communications processor (CP)
Compendium Part D - Operation and Maintenance (V9.0)
Operating Manual, 02/2018, A5E43228948-AA
47
5.4.2
Firmware update using S7-400 Flash memory card
You can also find the requirements for performing the firmware update in the Download
Entry of the respective CPU firmware. You can find an overview of the Download Entries of
the CPU firmware updates in the following FAQ: "Where do you find the latest operating
systems of S7-41x CPUs (https://support.industry.siemens.com/cs/ww/en/view/40945038)?"
5.5
Updating firmware of a communications processor (CP)
This section applies to Ethernet CP 443-1, PROFIBUS CP 443-5 Extended, and
PtP CP 341.
The requirements and steps are described in the manual titled "SIMATIC Process Control
System PCS 7 Service Support and Diagnostics" for the respective PCS 7 version.
NOTICE
Only perform a firmware update during operation if no redundancy faults are present, i.e.
the REDF LED is not lit, and you have ensured that both IMs of all the connected redundant
stations (e.g. ET 200M) are operating correctly. Otherwise, process mode may be
disrupted.

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals