AS and OS expansions
7.2 Program changes
Compendium Part D - Operation and Maintenance (V9.0)
84 Operating Manual, 02/2018, A5E43228948-AA
7.2.3
Measures for maintaining delta download capability
The following section describes the actions and guidelines you have to observe to continue
downloading changes in RUN.
Generating reference data
Note
The SIMATIC M
anager menu command "Options > Reference Data > Generate" cannot be
used in PCS
7, because it would require a complete download with the CPU in STOP.
The "Options > Chart Reference Data" function is provided in the CFC editor for PCS 7 to
display reference information about the chart folder.